Battery Storage Fire Safety: Thermal Runaway and Codes
Failures at grid battery storage sites have become much less frequent: EPRI found the failure rate per deployed gigawatt-hour fell 98% between 2018 and 2025, to a level comparable with large oil-filled transformers.[1][2] EPRI says the main danger is explosion from a buildup of flammable gas or an arc flash, chiefly to first responders; the NFPA 855 fire code governs installations in North America, and the UL 9540A test assesses how fire from thermal runaway spreads.[3][4][5]
Battery storage plants hold large amounts of energy in lithium-ion cells, and when one fails it can burn or explode. EPRI data show such failures have become much less frequent, and that newer designs fail less often.[1][6] This page covers how often they happen, what the hazards are and how codes try to contain them.
This page covers stationary grid and commercial battery systems. The failure data come from EPRI’s database, which does not include home batteries or electric vehicles; for home systems, see home battery storage explained.
How often failures happen
EPRI keeps a database of battery storage failures. It was started in 2021 after a series of lithium-ion battery fires in South Korea and an incident in Surprise, Arizona. It covers utility-scale and commercial systems and counts large thermal events: arc flash, fire or explosion.[7]
In an October 2026 white paper, EPRI found that the annual failure rate, measured in failures per deployed gigawatt-hour, fell 98% between 2018 and 2025.[1] It judged the rate comparable to that of large oil-filled transformers.[2] Failure rates fall with newer designs. Systems installed in 2018 had a high early-life failure rate, all of it in South Korea, where investigations pointed to integration quality, battery management controls and manufacturing defects.[6]
The battery cell is rarely the identified culprit. In EPRI’s 2024 root-cause analysis, the components that most often failed were balance-of-plant equipment and controls, though EPRI notes that finding the cause is hard once a fire has destroyed the evidence.[8]
Thermal runaway and explosion risk
A badly failing lithium-ion cell can go into thermal runaway, a failure that the UL 9540A fire test is designed to study.[5] EPRI warns that gases vented during thermal runaway can explode.[9] Damaged cells can also keep heating after the flames go out and can still hold electricity.[9]
EPRI identifies a buildup of flammable gas or an arc flash leading to explosion as the primary danger. Explosion hazards pose the greatest risk to first responders close to the system, and an explosion occurred in 6 of the 10 incidents with injuries or deaths.[3] Deflagration panels and ventilation can reduce the risk from gases vented during thermal runaway. Thermal runaway can continue in damaged cells, and damaged cells can hold stranded energy, an electrical hazard.[9]
EPRI reports no injuries or deaths in 93% of recorded incidents, and no member of the public suffered acute injury from a battery storage arc flash, fire or explosion. Eleven of the 150 incidents recorded from 2018 to 2025 involved injuries or deaths: 24 injuries and 4 deaths in all, one unconfirmed. Firefighters accounted for 22 of the injuries and 3 of the deaths.[10]
How fires are fought
For battery fires, EPRI says the defensive “monitor and contain” approach is well established.[11] Site design shapes how bad a fire gets. EPRI found indoor facilities over-represented among US failure incidents and calls preventing fire spread within and between units critical. It compares two similar-sized California sites: at Elkhorn in 2022, the layout limited damage to less than 1% of the system’s energy capacity, while the January 2025 incident at Moss Landing lasted several days.[12][13]
Codes and testing
In North America, battery storage systems are certified to the UL 9540 product standard. The fire code is NFPA 855, the standard for installing stationary energy storage systems. It was first published in 2020, is updated every three years and was most recently issued in 2026.[4]
According to UL, UL 9540A is the US and Canadian national standard for assessing how fire from thermal runaway spreads in a battery system, and the only consensus standard NFPA 855 explicitly cites for large-scale fire testing.[5] Local fire authorities rely on module, rack and installation-level UL 9540A test results when they review sites for permits.[5]
For the wider growth of grid batteries, see how grid-scale storage works and the energy storage tracker.
Read next
Next in the crash course
Direct lithium extraction (DLE) explained
How direct lithium extraction pulls lithium from brine without evaporation ponds, the main methods, their limits, and Arkansas's Smackover projects.
More in Batteries and energy storage
Questions readers ask
How often do battery storage systems catch fire?
Less often than before. EPRI found that the annual failure rate of lithium-ion storage systems, in failures per deployed gigawatt-hour, fell 98% between 2018 and 2025, and that the rate is comparable to that of large oil-filled transformers.[1][2]
Are battery storage fires dangerous to people nearby?
EPRI reports no injuries or deaths in 93% of recorded incidents and no acute injuries to members of the public. Between 2018 and 2025 it recorded 24 injuries and 4 deaths, one unconfirmed, mostly among firefighters, and explosions were the main danger.[10][3]
Sources
· 13 claims from 4 publishers
Each numbered claim is a statement we checked against the sources listed with it. Tap a number in the text to see its sources in place.
- [1]
EPRI's October 2026 white paper found that the annual failure rate of lithium-ion battery energy storage systems, measured in failures per deployed GWh, fell 98% between 2018 and 2025. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 · Key findings (retrieved 2026-11-21)
- [2]
EPRI found the failure rate of battery storage systems comparable to that of large oil-filled transformers. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 · Key findings (retrieved 2026-11-21)
- [3]
EPRI says the main danger in battery storage incidents is a buildup of flammable gas or arc flash leading to explosions, which pose the greatest risk to first responders close to the system; explosions occurred in 6 of the 10 incidents with injuries or deaths. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [4]
In North America, battery storage systems are certified to the UL 9540 product standard, and the applicable fire code is NFPA 855, first published in 2020, updated every three years and most recently issued in 2026. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [5]
UL says UL 9540A is the US and Canadian national standard for assessing fire propagation from thermal runaway in battery storage systems and the only consensus standard NFPA 855 explicitly cites for large-scale fire testing; EPRI says local authorities rely on module, rack and installation-level UL 9540A testing when siting and permitting systems. reportedas of 2026-11-21
- UL 9540A Test Method for Battery Energy Storage Systems (BESS) · UL Solutions · Secondary source (retrieved 2026-11-21)
- UL 9540A Test Method for Battery Energy Storage Systems (BESS) · UL Solutions · Secondary source (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [6]
EPRI found failure rates fall with newer designs; the 2018 vintage had a high early-life failure rate, all of it in South Korea, with investigations pointing to integration quality, battery management controls and manufacturing defects. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [7]
EPRI's failure incident database, started in 2021 after lithium-ion battery fires in South Korea and an incident in Surprise, Arizona, covers utility-scale and commercial and industrial systems; it counts large thermal events (arc flash, fire or explosion) and does not track home batteries or electric vehicles. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [8]
In EPRI's 2024 aggregate root-cause analysis, the most commonly failed components were balance-of-plant equipment and controls; the battery cell was rarely identified as the root cause, though that is hard to establish after a fire. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [9]
EPRI notes that gases vented during thermal runaway pose an explosion hazard that deflagration panels and ventilation can reduce, that thermal runaway can continue in damaged cells, and that damaged cells can hold stranded electrical energy. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 · Table 12 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [10]
EPRI reports that 93% of recorded battery storage incidents involved no reported injuries or deaths; 11 of 150 incidents in its database from 2018 to 2025 did, with 24 injuries and 4 deaths (1 unconfirmed), mostly among firefighters, and no member of the public suffered acute injury. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 · Key findings (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [11]
EPRI says the defensive "monitor and contain" approach is well established for battery storage fires. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 · p. 33 (retrieved 2026-11-21)
- [12]
EPRI found indoor battery facilities over-represented in US failure incidents and says preventing fire spread within and between units is critical; at the 2022 Elkhorn incident in California, the site's layout limited damage to less than 1% of its energy capacity, while the 2025 Moss Landing incident lasted several days. confirmedas of 2026-10-01
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- Risk Factors and Failure Statistics of Lithium Ion BESS (white paper 3002034920) · EPRI · Primary source · 2026-10-01 (retrieved 2026-11-21)
- [13]
On 16 January 2025 a fire broke out at Vistra's Moss Landing battery storage facility in Monterey County, California; it burned for several days, more than a thousand residents were temporarily evacuated, and a year later the cause was still unknown. confirmedas of 2026-01-16
- A Year Out From One of the World's Largest Battery Facility Fires · Inside Climate News · Secondary source · 2026-01-16 (retrieved 2026-10-10)
- A Year Out From One of the World's Largest Battery Facility Fires · Inside Climate News · Secondary source · 2026-01-16 · Read via WebFetch on 2026-11-21 (site returns 403 to scripts); browser check recommended (retrieved 2026-10-10)
- A Year Out From One of the World's Largest Battery Facility Fires · Inside Climate News · Secondary source · 2026-01-16 · Read via WebFetch on 2026-11-21 (site returns 403 to scripts); browser check recommended (retrieved 2026-10-10)
- Moss Landing battery storage fire flares up again, raising new safety fears in California · CalMatters · Secondary source · 2026-09-18 (retrieved 2026-10-10)
Revision history (1)
- Page created.
Created Nov 21, 2026. Last reviewed by an editor on Nov 22, 2026. Next scheduled review: May 5, 2027.